The Ex HK-7100A Combustible Gas Detector, based on catalytic principle, is designed for continuous detecting and monitoring of combustible gases in ambient air over the range of 0-100% LEL(lower explosive limit) and provides a 4~20mA output signal that can be connected to a controller, PLC,DCS or similar instrumentation.
. ADVANCED MCU TECHNOLOGY.
. SMT AND INGETAL DESIGN—Enhance performance and reliability.
. CURRENT TRANSMISSION–Extremely extends the distance of signal transmission.
. CENTRALIZED POWER SUPPLY AND REGIONAL POWER SUPPLY
. LED DISPLAY—Display real-time concentration and operating statues of detector.
. SIGNAL TRANSMISSION—Send measured concentration signal to controller.
. INDOOR AND OUTDOOR USE—Suitable for the harshest environmental conditions.
. UNIQUE MAGNETIC PEN DESIGN—Operate detector through magnetic pen.
. SELF-PROTECTION FUNCTION—Prevent high concentration gas from damaging detector.
. IMPORTED CATALYTIC COMBUSTION SENSOR—Advanced performance with stable measurement, high sensitivity, anti-poisoning, and resist influence.
. SENSOR DIAGNOSTIC FUNCTION—Provide alarm and prompt while sensor fault or ageing.
Display |
LED Display real-time concentration and operating statues of detector (including high alarm,low alarm,and fault alarm) |
Measurement |
Combustible Gases |
Principle |
Catalytic combustion |
Sample |
Method Diffusion |
Measurement Range |
(0-100)% LEL |
Resolution |
1% LEL |
Accuracy |
±5% LEL |
Response Time (T90) |
≤30 sec at 25oC |
Alarm Configuration |
Two levels alarm,the alarm concentration programmable |
Ambient Temperature |
-40 to 70oC (need to add heater under -20oC) |
Ambient Humidity |
≤93%RH at 40oC (no condensation) |
Atmosphere Pressure |
86-106KPa |
Output Signal |
4-20mA |
Transmission Distance |
≤ 1000m ( 2.5mm2) |
Power Supply |
24±6VDC (centralized power supply or regional power supply) |
Connection Method |
3-wires |
Power Consumption |
≤1W |
Storage Temperature |
-40 to 85oC |
Protection Grade |
IP66 |
Executive Standard |
Q/HDHKY024-2006 |